Fiber Optical Converter G.703-C37.94 E1 820nm Multimode
The 21-219 Fiber Optic IEEE C37.94 – G.703 E1 Converter extends distance and provides galvanic isolation between teleprotection equipment and the telecom network in substation environments. Its two independent IEEE C37.94 ports can be used for network redundancy or cross-redundancy in dual installations, ensuring high system reliability.
The converter also works seamlessly with the 21-216 Fiber Optic IEEE C37.94 – G.703 64 kbps Codirectional Converter, making it ideal when teleprotection devices lack C37.94 interfaces or when SDH/PDH networks mix E1 G.703 and 64 kbps G.703 ports across sites.
Functioning as an electro-optical multiplexer, the 21-219 maps two IEEE C37.94 optical ports into the standard G.703/704 E1 frame, enabling full SDH/PDH multiplexing and de-multiplexing. Synchronization is sourced either from the E1 network port or an internal 2048 kbps PDH-compliant clock, allowing use over leased lines with electrical E1 modems such as SHDSL.
- Two independent IEEE C37.94 fiber optical connections over a single E1
- Standards compliant for power substation installations i.e ABB, Hitachi, Siemens, Mitsubishi and many others
- 19″ mounting with only 200mm depth
- Single power supply range from 48VDC to 230VAC
Fiber optical link
- Data Speed 2048kbps
- Protocol IEEE C37.94
- Wave-lenght 820nm
- Fiber Multimode 50/125µm or 62,5/125µm, ST-connector
- Optical System Budget 13dB in 62,5/125µm. 9dB in 50/125µm fiber
- Typical distance 0-2km (3dB system margin for 50/125µm and 6dB for 62,5/125µm)
Galvanic
- Galvanic Data speed 2048kbps
- Galvanic Protocol G.703, E1
- Connector 2 x BNC , Coaxial cable
Power Supply
- DC 48V DC to 250V DC, ±20%
- AC 230V AC , ±20%, 50 60 Hz
- AC-connector IEC 320, 3-pin
Environmental
- Operating Temperature Range -25 to +55°
- Storage Temperature Range -40 to +85°
- Relative Humidity Operating 5 to 95%
- Relative Humidity Storage 5 to 95% non condensing
CE compliance
- Immunity EN 61000-6-2
- Emission EN 61000-6-4
- LVD EN 50187; RIV=250 V OVC=III
Mechanical
- Vibration IEC 60255-21-1 Class 2
- Shock IEC 60255-21-2 Class 2
- Seismic IEC 60255-21-3 Class 2
EMC compliance
- ESD IEC 60255-22-2 Class 3, contact 6kV, air 8kV
- Radiated IEC 60255-22-3 / IEEE/ANSI C37.94.2; 35V/m
- Burst Power IEC 60255-22-1 Class III
- Burst Communication IEC 60255-22-1 Class II; 0,5kV diff; 1kV common mode
- Fast Transient Power IEC 60255-22-4 Class IV
- Fast Transient Communication IEC 60255-22-4 Class II; 1kV
Insulation
- Dielectric Test IEC 60255-5, 2,0kV 1min
- Impulse Voltage Test IEC 60255 / EN50178 5kV / 6 kV
- Insulation Resistance IEC 60255-5; > 100Mohm at 500VDC
Dimensions and Weight
- Physical size Height 45mm, Width 483mm, Without brackets 380mm), Depth 173mm
- Weight 3 kg